onoae

CS Instruments Mobile Active/Reactive Power Meter CS PM 600

All measured data are transferred digitally (Modbus) to DS 500 mobile/ DS 400 mobile and can be recorded there.

Features

  • Magnetic voltage measuring tips for measuring the voltage during operation
  • Hinged current transformers encompass the conductors of the phases L1, L2, L3. This can also be done during operation

Applications

  • Mobile current/effective power meter with 3 external current transformers for big machines and plants
  • External current transformers for clamping around the phases (100 A or 600 A)
  • External magnetic measuring tip for measuring the voltage
  • Incl. connection cable for mobile current/effective power meter for mobile instruments, 5 m

Specifications

  • Parameters: Voltage (Volt)
    Current (Ampere)
    Cos phi
    Effective power (kW)
    Apparent power (kVA)
    Reactive power (kVar)
    Active energy (kWh)
    Power frequency (Hz)
    All parameters are transferred digitally to DS 500
    mobile /DS 400 mobile
  • Accuracy
    current measurement:
    Threshold values for current
    deviation. Loss angle according to IEC 60044-1.
    Current deviation in % at
    rated current in
    120% 1
    100% 1
    20% 1.5
    5% 3
  • Accuracy active
    energy:
    IEC 62053-21 Class 1
  • Sensor connections:
    3 x current transformers
    (L1,L2,L3,N)
    4 x voltage measurement
    (L1,L2,L3,N)
  • Interfaces: RS 485 (Modbus protocol)
  • Measuring
    range:
    Voltage measurement max.
    400 Volt
    Current measurement max.
    100 A or 600 A
  • Size current
    transformers:
    100 A / 1 A
    (max. 24 mm wire),
    600 A / 1 A
    (max. 36 mm wire)
  • Dimensions
    case:
    270 x 225 x 156 mm
    (B x H x T)
  • Operating temperature:
    – 10…+40 °C

Downloads

Datasheet : CS Instruments Mobile ActiveReactive Power Meter CS PM 600