onoae

Delta-Elektrogas CFK Burner control system

CFK device is designed to control gas burners in accordance with norm EN 746-2, for
intermittent or continuous operation. Different versions are available and many parameters are
configurable to have the best solution for every plant.

 

 

Features

CFK device is designed to control gas burners in accordance with norm EN 746-2, for
intermittent or continuous operation. Different versions are available and many parameters are
configurable to have the best solution for every plant.

Applications

Available in BASIC or FULL version.
Flame detection via either UV cell or ionization rod, even shared with ignition.
Possibility to use either electronic or winding transformers.
Burner status is visualized via a 7-segment display and led-bar.
Parameter setting via PC and USB device.
Provided with advanced self-diagnostic to assure a safe operation.
Voltage supplied to loads equal to voltage supplied to the device.
Housing available in polymeric material or die-casted aluminium.
Supervision of the burner can be implemented by traditional electrical wiring, or through built-in
communication line.
Designed and manufactured according to EN 298.

Features of FULL and BASIC versions:                                                                    Full               Basic

ST Fuel valve Output for (pilot burner) fuel valve.                                                 ✔                   ✔
ND Fuel valve Output for main burner fuel valve.                                                 ✔                   ✖
Air output Output for blower or air valve.                                                                ✔                   ✖
Air pressure switch Input from low air pressure switch.                                       ✔                   ✖
Burner on Output activated when burner is running.                                            ✔                   ✔
Burner lockout Output activated while in lockout.                                                  ✔                   ✔
Remote reset Input for reset from lockout.                                                                ✔                   ✔
Remote air control Input for remote control of air output.                                     ✔                   ✖
Start input 1 Input to start/stop the burner.                                                               ✔                   ✔
Start input 2                    Configurable input:
Hi-temp bypass              to start/stop the main burner
2n Flame sensor             or for indirect flame surveillance above 750°C                ✔                  ✖
or for independent main flame sensor.
Supply monitor Protection against over/undervoltage.                                             ✔                   ✔
TraxBus Interface for communication fieldbus.                                                           ✔                  ✔
Infrared Local configuration/control with smartphone app and USB device        ✔                  ✔
Diagnostic Display reports cycle status, lockouts and failures.                                  ✔                  ✔
Life counter Counter for ignition cycles and working times.                                       ✔                  ✔
Log memory Last 60 lockouts, failures and manual shutdowns.                                ✔                  ✔

Specifications

Voltage 230 – 115 VAC 50/60 Hz (-15/+10%)
Process inputs 230 – 115 – 48 – 24 VAC (max. 3 mA)
Power absorption 6 VA
Enclosure IP64
Fuse (replaceable) 3 A fast 5×20
Available load for
Output 250 VAC, 2 A cosϕ=0,7
Minimum ionization
current > 1 A (current limitation 1mA)
Detector line length 30 m max. (2 m in case of single rod)
Detector voltage 250 VAC
Detector insulation > 50 M
Working temperature -20°C / +60°C
Flame detection Ionization rod or UV cell
Overall Dimension 200 x 120 x 71 mm
Weight 850 gr (plastic case)
1200 gr (aluminium case)

Downloads

Datasheet : Delta-Elektrogas CFK Burner control system