Mitsubishi Electric 7011B Single Phase Ups

Mitsubishi Electric 7011B Single Phase Ups was specially designed to meet the requirements of high-power density applications. Pairing this battery with the Mitsubishi Electric 1100 series of UPS provides you with long runtimes with a minimal number of cabinets and reduced maintenance.

Loading...

Description

Mitsubishi Electric 7011B Single Phase Ups

Mitsubishi Electric 7011B Single Phase Ups was specially designed to meet the requirements of high-power density applications. Pairing this battery with the Mitsubishi Electric 1100 series of UPS provides you with long runtimes with a minimal number of cabinets and reduced maintenance. Pair the high power density with its 15-year design life and small footprint and the BLC04 lithium battery solution is a clear choice for demanding small UPS applications such as Edge Data Centers.

Choosing a reliable and safe energy storage vendor is of paramount importance. Mitsubishi Electric partners with the largest manufacturers of energy storage batteries in the world; their expertise in the design and manufacturing of lithium-ion modules paired with redundant control architectures creates one of the safest lithium-ion systems on the market. When you need your UPS battery to be as reliable as a Mitsubishi Electric UPS, look no further.

Features

  • Available in 6, 8, 10, & 12 kVA
  • Space saving footprint
  • Up to 91.5% efficient
  • Transformerless design using full IGBT power electronics LCD touchscreen display
  • Simple to start up, operate, and maintain
  • Internal batteries included; external batteries can be added to achieve longer runtimes

Applications

  • Individual computers
  • Small networks
  • Communications systems
  • Security systems
  • Point of sale systems

Specifications

Mitsubishi Electric 7011B Single Phase Ups
Rated Output kVA 6 8 10 12
Rated Output kW 4.2 5.6 7 8.4
AC INPUT
Configuration 1 phase 3 wire
Voltage 240/120V, 208/120V +10% to -30%
Frequency 50/60Hz +/-5%
Power Factor .98 Lagging
Reflected Current THD 4% typ. at 100% load; 7% typ. at 50% load
BATTERY
Type VRLA
Backup Time 10 Minutes 18 Minutes 18 Minutes 10 Minutes
Nominal Voltage 216 Vdc
Minimum Voltage 173 Vdc
Number of Cells 108
AC OUTPUT
Configuration 1 Phase 3 Wire
Voltage 240/120V, 208/120V
Voltage Stability +/-2% steady state
Voltage Unbalance 2% typical at 100% unbalanced load
Voltage THD 2.5% maximum with linear load
Transient Response +/-5%
Transient Recovery Time 50 ms
Frequency 50/60 Hz
Frequency Regulation +/-0.05% in free running mode
Phase Displacement 1deg Typical at 100% load
Power Factor 0.70
Power Factor Range 0.7 to 1.0 lag (within output kW rating)
Overload Capacity 105%-150% for 1 minute
Environmental
Cooling Forced Air
Operating Temperature 32°F to 104°F (0°C to 40°C). Recommended 59°F to 77°F (15°C to 25°C)
Relative Humidity 30% to 90% non considering
Altitude 0 to 3300 feet no derating
Location Temperature-controlled, indoor area free of conductive contaminants
Clearance Required Top: 23.5 in. Front: 39.2 in. Rear: 23.5 in.
GENERAL
Weight (lbs) 298 496 496 496
Dimensions (WxDxH) inch 13.8 x 29.9 x 27.8 13.8 x 29.9 x 40.6 13.8 x 29.9 x 40.6 13.8 x 29.9 x 40.6
Heat Rejection (kBTU/Hr) 1.4 1.9 2.4 2.8